POST EMERGENCY POWER INTERRUPTION REPORT

September 10, 2024, Tuesday

From 1:32 AM to 4:17 AM

Areas affected: Municipality of Ivisan and portion of the Municipalities of Panitan and Sigma
Feeder 4 at Panitan Substation experienced multiple tripping early morning today due to what was later discovered as damaged suspension insulator. The time and the circumstances of these line tripping were as follows:
• 1:32 AM to 1:32 AM – First tripping off due to unknown fault
• 1:33 AM to 2:12 AM – Second tripping off and where the disconnect switch at Barangay Ondoy, Ivisan was opened to isolate the fault. Feeder 4 was restored with the disconnect switch still open at Ondoy, Ivisan.
• 2:55 AM to 2:55 AM- Third tripping off upon testing
• 2:55 AM to 4:17 AM – Source of fault identified as damaged insulator at Parian-Mianay line section. The C8 jumper was opened at Barangay Parian, Sigma to isolate the fault and the load was transferred to Feeder 5R at Roxas City to temporarily power up the Municipality of Ivisan
 

Other News

EMERGENCY POWER INTERRUPTION

𝐄𝐌𝐄𝐑𝐆𝐄𝐍𝐂𝐘 𝐏𝐎𝐖𝐄𝐑 𝐈𝐍𝐓𝐄𝐑𝐑𝐔𝐏𝐓𝐈𝐎𝐍 Date: 𝐒𝐄𝐏𝐓𝐄𝐌𝐁𝐄𝐑 𝟐𝟒, 𝟐𝟎𝟐𝟔 (Thursday) Affected Areas: 𝐅𝐄𝐄𝐃𝐄𝐑 𝐅𝟑 - Whole...

read more

EMERGENCY POWER INTERRUPTION

𝐄𝐌𝐄𝐑𝐆𝐄𝐍𝐂𝐘 𝐏𝐎𝐖𝐄𝐑 𝐈𝐍𝐓𝐄𝐑𝐑𝐔𝐏𝐓𝐈𝐎𝐍 Date: 𝐒𝐄𝐏𝐓𝐄𝐌𝐁𝐄𝐑 𝟐𝟒, 𝟐𝟎𝟐𝟔 (Thursday) Affected Areas: 𝐅𝐄𝐄𝐃𝐄𝐑 𝐅𝟑 - Whole...

read more

EMERGENCY POWER INTERRUPTION

𝐒𝐂𝐇𝐄𝐃𝐔𝐋𝐄𝐃 𝐏𝐎𝐖𝐄𝐑 𝐈𝐍𝐓𝐄𝐑𝐑𝐔𝐏𝐓𝐈𝐎𝐍 SEPTEMBER 26, 2026 (Sabado nga adlaw) Ang CAPELCO magapatigayon sang...

read more

Follow Us

Other Related Posts